NEWS TAG
brand
Huiya Raised Floor Systems are also certified to the JIS A 1450:2009 standard by Japanese Industrial Standard / Japanese Standards Association, have been received great reputation in Japan markets. As a professional Raised Floor Manufacturer from China with over 15+ years experience, we have the ability to produce access floor systems according to JIS A 1450:2015 specifies the test methods for raised access floor for Japanese projects.
JIS A 1450:2015 Test Methods for Raised Access Floor
JIS A 1450:2015 specifies Test Methods for Raised Access Floor which is the supported standard by Japanese Industrial Standard / Japanese Standards Association. JIS A 1450:2015 Test Methods for Raised Access Floor cover the most important performance of access floor: Impact Load, Static Load, Rolling Load, Burning Test, Resistance Test, Antistatic test and Vibration Test.
Note: All the videos listed below are made by Jafa Free Access Floor Industry Association. If there is any infringement, please contact us to delete.
JIS A 1450:2015 Impact Load Test
Determine the impact of falling objects on the product
This test assumes the impact that occurs when a 20 kg copy paper stack is dropped in the office.
Drop the specified sandbag from a height of 250 mm to the weakest part of the product.
Evaluation
Residual deformation: 3.0 mm or less
Damage: Nothing
JIS A 1450:2015 Impact Load Test Process:
JIS A 1450:2015 Static Load Test
Determine the effect on the product when a desk or bookcase is placed
This is the test at the weakest part of the product, setting the most severe conditions for actual use.
Evaluation
Deformation amount: 5.0 mm or less
Amount of residual deformation: 3.0 mm or less
JIS A 1450:2015 Static Load Test Process:
JIS A 1450:2015 Rolling Road Test
Determine the effect on the product due to the traffic of the carrier
It is the test at the weakest part of the product, assuming the most severe conditions when actually used.
Running speed 10m-12m/min. 5,000 round trips with a dedicated tester
Evaluation
Amount of residual deformation: 3.0 mm or less
Damage: Record status
Rattling: record the condition
JIS A 1450:2015 Rolling Road Test Process:
JIS A 1450:2015 Inflammation Test
Determine product ignition resistance
The floor is not subject to interior restrictions, but it is a test assuming that the place where cables under the floor are dense is the source of fire.
Evaluation
Measure with flame only and self extinguish within 60 seconds
After flame time 0 seconds/Grade I 60 seconds or less/Grade II
JIS A 1450:2015 Inflammation Test Process:
JIS A 1450:2015 Anti-static Test
Determine if there is any effect of naturally occurring static electricity on the product
Static electricity generated by walking or moving a trolley may cause electric shock to the human body or malfunction of the computer, so measure the degree of electrification of the product.
Evaluation
U value (JIS A 1455) (antistatic performance evaluation value)
General offices: U≧0.6
Computer room, etc.: U≧1.2
JIS A 1450:2015 Anti-static Test Process:
JIS A 1450:2015 Leakage Resistance Test
Determine the range of vertical resistance of the product
This is a test to confirm the degree because the floor needs a proper resistance to prevent electric shock.
For safety, measure with the finishing material removed.
Evaluation
Resistance value R≧1.0×106Ω
JIS A 1450:2015 Leakage Resistance Test Process:
JIS A 1450:2015 Vibration Test
Determine the condition of the product after vibration due to an earthquake, etc.
This is a test to check whether it is possible to evacuate by walking on the floor after vibration, limiting it to OA floors of H200 mm or less such as offices.
(Applicable to floors of H300mm or less depending on the agreement between delivery parties)
Evaluation
Panel does not fall off
Panel damage, rise, gap, and horizontal movement are recorded.
JIS A 1450:2015 Vibration Test Process:
Welcome to Japan customers and raised floor distributor to contact us for building up a long-term and reliable cooperation, all our raised floor systems can be provided in accordance with JIS A 1450:2015 Test Methods, meet the requirements in Japan Industry.